Bosch Climate 5000 AC Error Codes: Indoor Unit Tables

Bosch Climate 5000 units report faults with a letter and a digit on the indoor display. The codes differ by indoor unit type, so check which type you have first. This guide uses the official Bosch service manual tables.

Which table applies to your unit

Bosch lists three indoor unit types: wall mounted, four-way cassette, and ducted. The same code can mean different things on different types, so match your unit type to the table before reading the code.

Wall mounted indoor unit

CodeMeaning
E0Indoor unit EEPROM error
E1Communication error between indoor and outdoor units
E3Indoor fan speed error
E4Indoor return air temperature sensor error
E5Indoor coil temperature sensor error
ECLow refrigerant
F0Outdoor current overload
F1Outdoor ambient temperature sensor error
F2Outdoor coil temperature sensor error
F3Compressor discharge temperature sensor error
F4Outdoor unit EEPROM error
F5Outdoor unit fan speed error
F6Indoor coil outlet temperature sensor error
P0Inverter module (IPM) error
P1High or low voltage protection
P3Outdoor unit low temperature lockout
P4Compressor drive error
P5Mode conflict

Four-way cassette indoor unit

CodeMeaning
E0Indoor EEPROM error
E1Indoor and outdoor unit communication malfunction
E3Indoor fan speed malfunction
E4Indoor room temperature sensor error
E5Evaporator coil temperature sensor error
ECRefrigerant leak detection system malfunction
EEWater level alarm malfunction
E8Dual indoor unit (twin) communication malfunction
E9Other twin model malfunction
F0Overload protection
F1Outdoor temperature sensor error
F2Outdoor condenser pipe sensor error
F3Discharge air temperature sensor error
F4Outdoor EEPROM error
F5Outdoor fan speed (DC fan motor) malfunction
F7Auto-lifting panel communication error
F8Auto-lifting panel malfunction
F9Auto-lifting panel is open
P0Inverter module IPM protection
P1High/low voltage protection
P2Compressor top overheating protection
P3Outdoor low temperature protection
P4Compressor drive error
P5Mode conflict
P6Compressor low-pressure protection
P7Outdoor IGBT sensor error

Ducted indoor unit

CodeMeaning
E0Indoor EEPROM error
E1Indoor and outdoor unit communication malfunction
E3Indoor fan speed malfunction
E4Indoor room temperature sensor error
E5Evaporator coil temperature sensor error
ECRefrigerant leak detection system malfunction
EEWater level alarm malfunction
E8Dual indoor unit (twin) communication malfunction
E9Other twin model malfunction
F0Overload protection
F1Outdoor temperature sensor error
F2Outdoor condenser pipe sensor error
F3Discharge air temperature sensor error
F4Outdoor EEPROM error
F5Outdoor fan speed (DC fan motor) malfunction
P0Inverter module IPM protection
P1High/low voltage protection
P2Compressor top overheating protection
P3Outdoor low temperature protection
P4Compressor drive error
P5Mode conflict
P6Compressor low-pressure protection
P7Outdoor IGBT sensor error
FAIndoor unit communication malfunction

What to do when you see a code

  1. Turn the unit off and note the code, the unit type and whether the code is on the indoor display or the remote.
  2. Clean the air filter and check that the indoor and outdoor units have clear airflow. Do this only with the unit off.
  3. Wait about 30 seconds, turn the unit back on, and check whether the code returns.
  4. If the code returns, or it is a P code, an F code, an E3 or EC, call a licensed Bosch technician. Do not open the outdoor unit or handle refrigerant or electrical parts yourself.

Sources

  • Bosch Climate 5000 Series Ductless Air Conditioner / Heat Pump Outdoor Unit Service Manual, Section 6 Error Codes (05.2025): Bosch service manual PDF
Scroll to Top